C00592 | resp. to can bus connection, C00593 | resp. to canx_in monitoring, C00592/2 – Lenze E84DGFCC User Manual
Page 86: C00593/1, C00593/2, C00592/5, Communication manual 8400 motec canopen

Communication manual 8400 motec CANopen
Parameter reference
Parameters for CANopen communication
86
L
EDS84DMOTCAN EN 3.0 - 11/2011
C00592
C00593
Parameter | Name:
C00592 | Resp. to CAN bus connection
Data type: UNSIGNED_8
Index: 23983
d
= 5DAF
h
Configuration of monitoring of the CAN interface
Selection list
0 No Reaction
1 Fault
2 Trouble
4 WarningLocked
Subcodes
Lenze setting
Info
C00592/1
0: No Reaction
Response to an incorrect telegram during CAN
communication
C00592/2
0: No Reaction
Response to "BusOff" (bus system switched off)
C00592/3
0: No Reaction
Response to warnings of the CAN controller
C00592/4
0: No Reaction
Response to communication stop of a CAN bus node
C00592/5
0: No Reaction
Response to an event in the case of monitoring via
heartbeat protocol
;
Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C00593 | Resp. to CANx_IN monitoring
Data type: UNSIGNED_8
Index: 23982
d
= 5DAE
h
Configuration of monitoring for the reception of PDOs CAN1_IN and CAN2_IN
Selection list
0 No Reaction
1 Fault
2 Trouble
4 WarningLocked
Subcodes
Lenze setting
Info
C00593/1
0: No Reaction
Response if the monitoring time set in
for the
reception of the PDO CAN1_IN is exceeded.
C00593/2
0: No Reaction
Response if the monitoring time set in
for the
reception of the PDO CAN2_IN is exceeded.
;
Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT