I-1006 - Communication cycle period
Setting the sync telegram cycle time.
The cycle time can be selected as "1000" or as an integer multiple of it.
If "0 μs" is set
(Lenze setting), no sync telegrams are generated.
This object relates to code
I-1014 - COB-ID EMCY
When communication errors occur and are acknowledged or when internal errors occur in
the communication module or controller (e.g. "fault"), an error message is sent on the
system bus. The telegram is sent once for every error. This function can be activated or
deactivated with bit 31.
[13-3] Data telegram assignment
Index:
I-1006
Name:
Communication cycle period
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: Communication cycle period
0 μs
0
μs
65535000 rw
U32
Index:
I-1014
Name:
COB-ID EMCY
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: COB-ID EMCY
0x80 + node ID
0
4294967295 rw
U32
8th byte
7th byte
6th byte
5th byte
Data 4
Data 3
Data 2
Data 1
Bit 31
Bit 30
Bit 29 ... bit 11
Bit 10 ... bit 0
0/1
0
Extended identifier*
11-bit identifier
* The extended identifier is not supported - bit 11 ... bit 29 must be set to "0".
Bit
Setting
Bit 31
0 Emergency object is valid.
1 Emergency object is invalid.
Note!
The identifier can only be changed in the "emergency object invalid" status
(bit 31 = 1).