I-1018 - identity object, I-1200 - sdo1 server parameter, I-1018 – Lenze E84DGFCC User Manual
Page 96: I-1200, Communication manual 8400 motec canopen, Implemented canopen objects

Communication manual 8400 motec CANopen
Implemented CANopen objects
96
L
EDS84DMOTCAN EN 3.0 - 11/2011
I-1018 - Identity object
I-1200 - SDO1 server parameter
Identifiers for SDO server channel 1 (basic SDO channel).
According to DS301 V4.02, the basic SDO channel can neither be changed nor deactivated.
[13-5] Data telegram assignment
Index:
I-1018
Name:
Identity object
Subindex
Default setting
Display range (min. value | unit | max. value)
Access
Data type
0: Highest subindex supported
See below
0
4294967295 ro
U32
1: Vendor ID
2: Product code
3: Revision number
4: Serial number
Subindex
Meaning
1
Manufacturer's identification number
• The identification number allocated to Lenze by the organisation "CAN in
Automation e. V." is "0x0000003B".
2
Product code
3
Main version and subversion of firmware
4
Serial number
Index:
I-1200
Name:
SDO1 server parameter
Subindex
Default setting
Display range (min. value | unit | max. value)
Access
Data type
0: Highest subindex supported
2
2
2 ro
U8
1: COB-ID client -> server (rx)
Node ID + 0x600
0
4294967295 ro
U32
2: COB-ID server -> client (tx)
Node ID + 0x580
0
4294967295 ro
U32
Subindex
Meaning
1
Specification of the receive identifier
• For SDO server channel 1: node address (C00350) + 0x600
2
Specification of the transmit identifier
• For SDO server channel 1: node address (C00350) + 0x580
8th byte
7th byte
6th byte
5th byte
Data 4
Data 3
Data 2
Data 1
Bit 31
Bit 30
Bit 29 ... bit 11
Bit 10 ... bit 0
0
0
Extended identifier*
11-bit identifier