I-1800 - tpdo1 communication parameter, I-1800/1, I-1800 – Lenze E84DGFCC User Manual
Page 102: I-1800/2, Communication manual 8400 motec canopen, Implemented canopen objects
![background image](/manuals/565821/102/background.png)
Communication manual 8400 motec CANopen
Implemented CANopen objects
102
L
EDS84DMOTCAN EN 3.0 - 11/2011
I-1800 - TPDO1 communication parameter
Communication parameters for sending process data via TPDO1
[13-15] Data telegram assignment
How to change the identifier:
1. Deactivate identifier (set bit 31 to "1").
2. Change identifier.
3. Activate identifier (set bit 31 to "0").
Index:
I-1800
Name:
TPDO1 communication parameter
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: Highest subindex supported
5
- (read access only)
ro
U8
1: COB-ID used by TPDO
0x180 + node ID
0
4294967295 rw
U32
2: Transmission type
254
0
255 rw
U8
3: Inhibit time
0 ms
0
0.1 ms
65535 rw
U16
4: Reserved
-
- (reserved, read or write access results in error
message 0x06090011)
rw
U8
5: Event timer
0 ms
0
ms
65535 rw
U16
Subindex
Meaning
Code
0
The value 5 is permanently set.
• Max. 5 subindexesare supported.
-
1
TPDO1 identifier
• According to the "Predefined Connection Set", the
basic setting is: identifier = 0x180 + node ID
2
TPDO transmission type according to DS301 V4.02
3
Minimum time between sending two identical TPDOs
(see DS301 V4.02).
-
5
Cycle time for PDO transmission with transmission type
"254".
8th byte
7th byte
6th byte
5th byte
Data 4
Data 3
Data 2
Data 1
Bit 31
Bit 30
Bit 29 ... bit 11
Bit 10 ... bit 0
0/1
0/1
Extended identifier*
11-bit identifier
* The extended identifier is not supported - bit 11 ... bit 29 must be set to "0".
Bit
Setting
Bit 30
0 RTR to this PDO permissible (Lenze).
1 RTR to this PDO not permissible (cannot be set).
Bit 31
0 PDO active
1 PDO inactive