Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17

99

14

Parameter reference

14.2

Parameters of the communication module for slot MXI1

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C13886

C13887

Parameter | Name:

C13886 | Set ext. diagnostic bit upon

Data type: BITFIELD_8

Index: 10689

d

= 29C1

h

Bit-coded selection of the error responses in the standard device causing the external diagnostic bit ("diag bit") to

be set (see PROFIBUS specification; bit 3 of byte 1 of the DP diagnostic messages).

• The diagnostic bit is sent to the PROFIBUS master where it is evaluated separately.

• The diagnostic bit is always set when a system error occurs.

• The Lenze setting "0" means that the diagnostic bit is not set for the following error responses.

• An advanced diagnostic message is always sent.

Value is bit-coded:

Bit 0 Error
Bit 1 Trouble
Bit 2 Quick stop by trouble
Bit 3 Warning locked
Bit 4 Warning
Bit 5 Reserved
Bit 6 Reserved
Bit 7 Reserved

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C13887 | Suppress signalling diag. mess. upon

Data type: BITFIELD_8

Index: 10688

d

= 29C0

h

Available from software version 01.20!

Selection of the error responses not causing a diagnostic request to the PROFIBUS master.

A diagnostic request is always signalled if a system error or an error message from the SM301 (E94AYAE) safety

module occurs.

The Lenze setting "0" means that for each of the following error responses a diagnostic request is signalled.
Value is bit-coded:

Info

Bit 0 Error
Bit 1 Trouble
Bit 2 Quick stop by trouble
Bit 3 Warning locked
Bit 4 Warning
Bit 5 Reserved
Bit 6 Reserved
Bit 7 Error message

0x00c88130

Available from software version 01.21!

Selective suppression of the error message "Available

connection to 9400 standard device lost"

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT