4 error codes, Error codes, 9parameter data transfer – Lenze E94AYCPM User Manual
Page 70
9
Parameter data transfer
9.3
PROFIdrive parameter data channel (DP-V1)
70
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.3.4
Error codes
Error code
Description
Explanation
Additional
information
0x0000
Impermissible parameter
number
Access to unavailable parameter
-
0x0001
Parameter value cannot be
changed
Change access to a parameter value that cannot be
changed
Subindex
0x0002
Lower or upper value limit
exceeded
Change access with value beyond the value limits
Subindex
0x0003
Faulty subindex
Access to unavailable subindex
Subindex
0x0004
No array
Access with subindex to non-indicated parameter
-
0x0005
Wrong data type
Change access with value that does not match the
data type of the parameter
-
0x0006
No setting permitted (only
resettable)
Change access with value unequal to 0 where this is
not permitted
Subindex
0x0007
Description element cannot
be changed
Change access to a description element that cannot
be changed
Subindex
0x0008
Reserved
(PROFIdrive profile V2: PPO-Write requested in the IR
is not available)
-
0x0009
Description data not
available
Access to unavailable description (parameter value is
available)
-
0x000A
Reserved
(PROFIdrive profile V2: Wrong access group)
-
0x000B
No parameter change rights Change access without parameter change rights
-
0x000C
Reserved
(PROFIdrive profile V2: Wrong password)
-
0x000D
Reserved
(PROFIdrive profile V2: Text in the cyclic traffic
cannot be read)
-
0x000E
Reserved
(PROFIdrive profile V2: Name in the cyclic traffic
cannot be read)
-
0x000F
No text array available
Access to unavailable text array (parameter value is
available)
-
0x0010
Reserved
(PROFIdrive profile V2: Missing PPO-Write)
-
0x0011
Request cannot be executed
due to the operating state
Access is not possible due to temporary reasons not
specified here
-
0x0012
Reserved
(PROFIdrive profile V2: Other error)
-
0x0013
Reserved
(PROFIdrive profile V2: date in the cyclic traffic
cannot be read)
-
0x0014
Value impermissible
Change access with the value that is inside the value
limits but not permissible for other permanent
reasons (parameters with defined individual values)
Subindex
0x0015
Response too long
The length of the current response exceeds the
maximum transmittable length
-
0x0016
Parameter address
impermissible
Impermissible or non-supported value for attribute,
number of subindices, parameter number, or
subindex, or a combination
-
0x0017
Format impermissible
Write request: Impermissible or non-supported
format of parameter data
-
0x0018
Number of values not
consistent
Write request: Number of values of the parameter
data do not match the number of subindices in the
parameter address
-
0x0019
Reserved
-
-
...
0x0064