1 reading parameter data from the controller, Reading parameter data from the controller, 9parameter data transfer – Lenze E94AYCPM User Manual
Page 61
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
61
9
Parameter data transfer
9.3
PROFIdrive parameter data channel (DP-V1)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.3.3.1
Reading parameter data from the controller
Request header
Parameter attribute
Index and subindex
Note!
• When a read request is processed, no parameter value is written to the slave.
• In the case of a multi-parameter read request, the parameter attribute, index, and
subindex are repeated with the number "n" of the requested parameters.
• A read request must not exceed the maximum data length of 240 bytes.
Byte 1
Byte 2
Byte 3
Byte 4
Request reference
Request identification
Axis
Number of indices
Field
Data type
Values
Request reference
U8
This value is specified by the master
Request identification
U8
0x01: Request parameters for reading
Axis
U8
0x00 or 0x01
Number of indices
U8
0x"n" (n = number of parameters requested)
Byte 5
Byte 6
Attribute
Number of subindices
Field
Data type
Values
Attribute
U8
0x10: Value
Number of subindices
U8
0x00
(For array elements: Enter the number of array elements
required.)
Byte 7
Byte 8
Byte 9
Byte 10
Index
Subindex
High byte
Low byte
High byte
Low byte
Field
Data type
Values
Index
U16
0x0001 ... 0xFFFF (1 ... 65535)
Subindex
U16
0x0001 ... 0xFFFF (1 ... 65535)