beautypg.com

1 reading parameter data from the controller, Reading parameter data from the controller, 9parameter data transfer – Lenze E94AYCPM User Manual

Page 61

background image

Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17

61

9

Parameter data transfer

9.3

PROFIdrive parameter data channel (DP-V1)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.3.3.1

Reading parameter data from the controller

Request header

Parameter attribute

Index and subindex

Note!

• When a read request is processed, no parameter value is written to the slave.
• In the case of a multi-parameter read request, the parameter attribute, index, and

subindex are repeated with the number "n" of the requested parameters.

• A read request must not exceed the maximum data length of 240 bytes.

Byte 1

Byte 2

Byte 3

Byte 4

Request reference

Request identification

Axis

Number of indices

Field

Data type

Values

Request reference

U8

This value is specified by the master

Request identification

U8

0x01: Request parameters for reading

Axis

U8

0x00 or 0x01

Number of indices

U8

0x"n" (n = number of parameters requested)

Byte 5

Byte 6

Attribute

Number of subindices

Field

Data type

Values

Attribute

U8

0x10: Value

Number of subindices

U8

0x00

(For array elements: Enter the number of array elements

required.)

Byte 7

Byte 8

Byte 9

Byte 10

Index

Subindex

High byte

Low byte

High byte

Low byte

Field

Data type

Values

Index

U16

0x0001 ... 0xFFFF (1 ... 65535)

Subindex

U16

0x0001 ... 0xFFFF (1 ... 65535)