C00637 | resp. to new module in mxi2, C01501 | resp. to comm. error with mxi1, C01502 | resp. to comm. error with mxi2 – Lenze E94AYCPM User Manual
Page 92: C01501, C01502, Module, In slot mxi2), 14 parameter reference

14
Parameter reference
14.1
Communication-relevant parameters of the standard device
92
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00637
C01501
C01502
Parameter | Name:
C00637 | Resp. to new module in MXI2
Data type: UNSIGNED_32
Index: 23939
d
= 5D83
h
Response when a new module has been inserted in module slot 2 of the standard device.
Selection list
(Lenze setting printed in bold)
1 Error
6 Information
5 Warning
4 Warning locked
3 Quick stop by trouble
0 No response
;
Read access ; Write access CINH PLC-STOP No transfer
Parameter | Name:
C01501 | Resp. to comm. error with MXI1
Data type: UNSIGNED_32
Index: 23074
d
= 5A22
h
Response to a communication error between an "intelligent" module in module slot 1 and the standard device
Selection list
(Lenze setting printed in bold)
0 No response
1 Error
3 Quick stop by trouble
4 Warning locked
5 Warning
;
Read access ; Write access CINH PLC-STOP No transfer
Parameter | Name:
C01502 | Resp. to comm. error with MXI2
Data type: UNSIGNED_32
Index: 23074
d
= 5A22
h
Response to a communication error between an "intelligent" module in module slot 2 and the standard device
Selection list
(Lenze setting printed in bold)
0 No response
1 Error
3 Quick stop by trouble
4 Warning locked
5 Warning
;
Read access ; Write access CINH PLC-STOP No transfer