C13867 | display: most recent diagnostic data, C13868 | display: dp state, C13880 | reaction on communication fault – Lenze E94AYCPM User Manual
Page 97: Terised under, C13880/1, C13868, C13880/2, 14 parameter reference
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
97
14
Parameter reference
14.2
Parameters of the communication module for slot MXI1
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13867
C13868
C13880
Parameter | Name:
C13867 | Display: Most recent diagnostic data
Data type: OCTET_STRING
Index: 10708
d
= 29D4
h
Display of the last diagnostic data sent to the PROFIBUS master (ASCII string with 16 characters)
Advanced diagnostic message ( 85)
;
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13868 | Display: DP state
Data type: UNSIGNED_8
Index: 10707
d
= 29D3
h
Available from software version 01.21!
Display of the DP states (Decentralized Peripherals)
Short-time interruption of PROFIBUS communication ( 79)
, see fig.
Selection list
(read only)
0 Waiting for parameterisation
1 Waiting for configuration
2 Data exchange
3 n/a
;
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13880 | Reaction on communication fault
Data type: UNSIGNED_8
Index: 10695
d
= 29C7
h
Monitoring response to a communication fault on the PROFIBUS
A change in the monitoring response is effective immediately.
Permanent interruption of PROFIBUS communication ( 78)
Selection list
0 No response
1 Error
3 Quick stop by trouble
4 Warning locked
6 Information
Subcodes
Lenze setting
Info
C13880/1
0: No response
The response set here for the "Watchdog/Data
Exchange" monitoring function is executed if the bus
station ...
• does not receive a message from the master within
the watchdog monitoring time (displayed in
) if there is an active connection.
• detects that it is no longer in the "Data_Exchange"
status. Please see also the notes given under
C13880/2
0: No response
The response set here for the "DPV1 MSAC2" monitoring
is executed if the bus station does not receive a "DPV1
MSAC2" message from the master within the monitoring
time (displayed in
) if there is an active
connection) and the MSAC2 connection is stopped by the
slave.
Note: We recommend only setting "information" as
response so that no drive-relevant response is executed.
;
Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT