Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
31
6
Commissioning
6.3
Possible DIP switch settings
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.3
Possible DIP switch settings
[6-1]
DIP switch
6.3.1
Setting the station address
The station addresses must differ from each other if several networked PROFIBUS stations are used.
The station address can be set via the DIP switches 1 ... 64 or via the »Engineer« (code
/
).
The housing labelling indicates the valencies of the individual DIP switches for setting the station
address.
• Valid address range: 1 … 126 (max. 126 slave stations)
•
: Display of the current address setting of the switches
•
: Display of the station address active on the PROFIBUS
E94YCPM001D
The front-panel DIP switches can be used to set:
• The station address (switches 1 ... 64)
• Compatibility with the communication module EMF2133IB
(switch 2133)
Lenze setting: all switches in OFF position
Setting the station address via ...
DIP switch
C13899 / 14899
Condition
At least one switch 1 … 64 = ON
• Switches 1 ... 64 = OFF
• Switch 1 ... 64 = ON
(invalid value "127")
DIP switch
64
32
16
8
4
2
1
Switch position
OFF
OFF
ON
OFF
ON
ON
ON
Value
0
0
16
0
4
2
1
Station address
= sum of the valencies = 16 + 4 + 2 + 1 = 23
DIP switch positions for setting the station address ( 116)
Note!
Switch off the voltage supply of the communication module and then on again in order
to activate changed settings.