14
Parameter reference
14.1
Communication-relevant parameters of the standard device
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
14
Parameter reference
This chapter supplements the parameter list and the table of attributes contained in the software
manual and in the »Engineer« online help for the Servo Drive 9400 with the parameters of the
E94AYCPM (PROFIBUS) communication module.
14.1
Communication-relevant parameters of the standard device
This chapter lists the communication-relevant parameters of the Servo Drive 9400 in numerically
ascending order.
C00615
C00636
Software manual/»Engineer« online help for Servo Drive 9400
Here you can find general information on parameters.
Parameter | Name:
C00615 | Resp. to imp. device conf.
Data type: UNSIGNED_32
Index: 23960
d
= 5D98
h
Response to incorrect device configuration
Selection list
1 Error
3 Quick stop by trouble
4 Warning locked
6 Information
0 No response
Subcodes
Lenze setting
Info
C00615/1
0: No response
Reserved
C00615/2
1: Fault
Resp. to imp. module in MXI1
C00615/3
1: Fault
Resp. to imp. module in MXI2
C00615/4
0: No response
Reserved
C00615/5
0: No response
Reserved
;
Read access ; Write access CINH PLC-STOP No transfer
Parameter | Name:
C00636 | Resp. to new module in MXI1
Data type: UNSIGNED_32
Index: 23939
d
= 5D83
h
Response when a new module has been inserted in module slot 1 of the standard device.
Selection list
(Lenze setting printed in bold)
1 Error
6 Information
5 Warning
4 Warning locked
3 Quick stop by trouble
0 No response
;
Read access ; Write access CINH PLC-STOP No transfer