2 possible causes and remedies, Profibus: no memory access [0x00c85531, Profibus: read memory error [0x00c85532 – Lenze E94AYCPM User Manual
Page 88: Profibus: write memory error [0x00c85533, Profibus: restart after watchdog reset [0x00c86010, Possible causes and remedies, 0x00c83100, 0x00c85531, 0x00c85532, 0x00c85533

13
Error messages
13.2
Possible causes and remedies
88
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
13.2
Possible causes and remedies
This chapter lists all PROFIBUS error messages in the numerical order of the error numbers. Possible
causes and remedies as well as responses to the error messages are described in detail.
Profibus: Lost connection to 9400 standard device [0x00c83100]
Profibus: No memory access [0x00c85531]
Profibus: Read memory error [0x00c85532]
Profibus: Write memory error [0x00c85533]
Profibus: Restart after watchdog reset [0x00c86010]
Response (Lenze setting printed in bold)
Setting: not possible
:
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
• Network cable (plug) is defective.
• Network cable is not connected to the PROFIBUS
terminal X201.
• Voltage supply is interrupted.
Check cables and terminals.
Connect network cable to the PROFIBUS terminal X201.
Response (Lenze setting printed in bold)
Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning : Information
Cause
Remedy
Access to memory was not possible.
Repeat the download of the application
(including module)
Response (Lenze setting printed in bold)
Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning : Information
Cause
Remedy
Parameter could not be read.
Repeat the download of the application
(including module)
Response (Lenze setting printed in bold)
Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning : Information
Cause
Remedy
Parameter could not be written.
Repeat the download of the application
(including module)
Response (Lenze setting printed in bold)
Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Module defective.
If this occurs repeatedly, contact the Lenze service.