11 monitoring – Lenze E94AYCPM User Manual
Page 79

Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
79
11
Monitoring
11.2
Short-time interruption of PROFIBUS communication
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
11.2
Short-time interruption of PROFIBUS communication
From software version 01.21, the current DP states are displayed in C13868 / C14868.
[11-1] DP states (Decentralized Peripherals) for short-time interruption of communication
The master detects the communication fault and transfers the slave to the "WAIT_PRM" state of the
DP state machine after only a few microseconds (see Fig.
Only after the state chain of the DP state machine ending in the "Data_Exchange" state
(DATA_EXCH) has been passed through, the watchdog monitoring time calculated for the slave (in
milliseconds) continues to run.
Additional monitoring for the data exchange
An additional monitoring function for data exchange is available under
/
. This
monitoring function already becomes active when the "Data_Exchange" state is exited and the
parameterised time (0 ... 65535 ms) has expired. The active monitoring function triggers the
/
2133PFB006
POWER ON
WAIT_PRM
WAIT_CFG
DATA_EXCH
Slave_Diag
Get_Cfg
Set_Slave_Add
Slave_Diag
Chk_Cfg, not o.k.
Set_Prm, not o.k.
Chk_Cfg, o.k.
Slave_Diag
Set_Prm
Get_Cfg
Note!
The watchdog monitoring time does not continue to run when the slave does not reach
the "Data_Exchange" state due to repeated communication errors (e.g. caused by loose
contact).
Note!
Observe the following condition for the time setting:
Monitoring time for data exchange (
≤
watchdog monitoring time of
PROFIBUS (
/
).