C13881

C13882

C13885

Parameter | Name:

C13881 | Monitoring time: Data exchange

Data type: UNSIGNED_16

Index: 10694

d

= 29C6

h

If the "Data Exchange" state is exited, the response parameterised under

C13880/1

is carried out when the

monitoring time for data exchange set here has expired.

• A value of "65535" in this code deactivates the monitoring function.

• A change in monitoring is effective immediately.

• The value set here for the monitoring time must be smaller than the watchdog monitoring time (

C13882/1

).

Permanent interruption of PROFIBUS communication ( 78)

Setting range

(min. value | unit | max. value)

Lenze setting

0

ms

65535 65535 ms

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C13882 | Monitoring time: Watchdog

Data type: UNSIGNED_32

Index: 10693

d

= 29C5

h

Display of the watchdog monitoring time determined by the PROFIBUS master

• A change in the watchdog monitoring time is immediately effective.

• Monitoring starts with the receipt of the first telegram.

• When a value of "0" is displayed, the monitoring function is deactivated.

Permanent interruption of PROFIBUS communication ( 78)

Display area

(min. value | unit | max. value)

0

ms

4294967295

Subcodes

Info

C13882/1

Watchdog monitoring time

C13882/2

DP-V1 MSC2

;

Read access … Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C13885 | Clear process data

Data type: UNSIGNED_8

Index: 10690

d

= 29C2

h

Selection of the process data which the controller will process in the event of a PROFIBUS failure in order to maintain

internal communication.
Selection list

(Lenze setting printed in bold)

0 Use of most recent master PDOs
1 PDOs are set to the value '0'

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT