5.2.3
Bus cable specification
Bus cable length
The length of the bus cable depends on the baud rate and cable type used. The data in the following
table applies to PROFIBUS cables of "FC-Standard Cable" cable type .
Tip!
We recommend taking the use of optical fibres into consideration for high baud rates.
Advantages of optical fibres:
• External electromagnetic interferences have no effect on the transmission path.
• Bus lengths of several kilometres are also possible with higher baud rates.
• The bus length is ...
• independent of the baud rate;
• dependent on the optical fibre used.
Note!
Only use cables which meet the listed specifications of the PROFIBUS user organisation.
Area
Values
Cable resistance
135 ... 165 Ω/km, (f = 3 ... 20 MHz)
Capacitance per unit length
≤
30 nF/km
Loop resistance
< 110 Ω/km
Core diameter
> 0.64 mm
Core cross-section
> 0.34 mm
2
Cores
Twisted in pairs, insulated and shielded
Baud rate
Length
9.6 ... 93.75 kbps
1200 m
187.5 kbps
1000 m
500 kbps
400 m
1500 kbps
200 m
3000 ... 12000 kbps
100 m
Note!
The baud rate depending of the data volume, cycle time and number of stations should
only be selected as high as required for the application.