12.3.1
Example 1: Error in parameter data "Incorrect PROFIsafe target address"
This error was caused while communication of the PROFIBUS master was established because the
PROFIsafe target address configured in the PROFIBUS master does not correspond to the set address
anymore.
12.3.2
Example 2: Error "Undervoltage in the DC bus" in the Servo Drive 9400
Byte
Value
[hex]
Description
1
x Standard data (PRM_Fault)
...
6
7
0A Block length of the advanced diagnostics = 10 bytes
8
81 Status message
9
00 Slot 0
10
01 Status coming
11
40 PROFIsafe error "0x0040" (64)
GSG: "F address differ to F_Dest_Add"
12
00
13
00 No other error message
...
...
16
00
Byte
Value
[hex]
Description
1
x Standard data (PRM_Fault)
...
6
7
0A Block length of the advanced diagnostics = 10 bytes
8
81 Status message
9
00 Slot 0
10
01 Status coming
11
00 No PROFIsafe/safety error
12
00
13
0F Error message 0x447B000F "Undervoltage in DC bus"
• Response: "Fault"
• Instance ID: 1
• Module ID: 0x7B
• Error ID: 0x0F
14
00
15
7B
16
44