9 parameter data transfer, 1 addressing of the parameter data, Parameter data transfer – Lenze E94AYCPM User Manual
Page 47: Addressing of the parameter data, 9parameter data transfer

Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
47
9
Parameter data transfer
9.1
Addressing of the parameter data
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9
Parameter data transfer
The E94AYCPM communication module supports the cyclic and acyclic transmission of parameter
data:
• Cyclic DP-V0 parameter data are based on the DRIVECOM profile.
If the parameter data channel is active according to DP-V0, it is assigned an additional 4 words
of input / output data.
• Acyclic DP-V1 parameter data are based on the PROFIdrive profile.
9.1
Addressing of the parameter data
The parameter data are addressed via codes which can be found in this documentation and in the
corresponding documentation of your controller.
Addressing of Lenze parameters
In the case of the DP-V0 parameter data channel, the parameters of a device are not addressed
directly via Lenze code numbers, but via indices (bytes 3 + 4) and subindices (byte 2).
The conversion is made via an offset (24575 / 0x5FFF):
• PROFIBUS-DP index
dec
= 24575 - Lenze code number
• PROFIBUS-DP index
hex
= 0x5FFF - Lenze code number
hex
Example of C00105 (quick stop deceleration time):
• PROFIBUS-DP index
dec
= 24575 - 105 = 24470
• PROFIBUS-DP index
hex
= 0x5FFF - 0x69 = 0x5F96
The parameter values are entered into the user data (bytes 5 to 8) of the telegram.