beautypg.com

Lenze 8400 protec Manual User Manual

Page 97

background image

Electrical installation − HighLine/StateLine version

Control terminals

Digital inputs and outputs

6

l

97

EDS84DPS424 EN 5.0

Digital outputs

)

Note!

If inductive loads are being connected, it is essential to use a spark suppressor
at the digital output.

X42 − digital outputs DO1, DO2 (configured digital input!)

Pin

Signal

Description

Data

Type M12, 5−pole sockets

84DPSO05_5

1

24O

24 V supply of the external sensors

2

DO2

digital output 2 (configured)

HIGH

+24 V or V

DC

at X10

3

GIO

Reference potential

LOW

0 ... +5 V

4

DO1

digital output 1 (configured)

max. 200 mA per output

5

n. c.

Not assigned

Example circuit

0

1

DO1

X42

GND-IO

GIO

24O DO2

8400DIO016

Fig. 6−7

Wiring examples of the digital inputs and outputs
0

Digital control (relay, valve, ...) with internal 24 V supply

1

X42

Plug for the digital outputs (configured)

GIO

Ground reference potential for the digital inputs and outputs (GND−IO)