Canopen, Can on board, Communication canopen – Lenze 8400 protec Manual User Manual
Page 101: 3 canopen, Example circuit wiring example, Can communication, Parameter setting and configuration, System bus (can) diagnostics

Electrical installation − HighLine/StateLine version
Communication
CANopen®
l
101
EDS84DPS424 EN 5.0
6.7.3
CANopen®
X3x − communication
Pin
Signal
Description
Data
Type: M12, 5−pole, A−coded
X31 −> pins
X32 −> sockets
84DPSO05_5
1
n. c.
Not assigned
CAN specification
2
n. c.
Not assigned
3
CG
CAN−Ground
4
CH
CAN−HIGH
5
CL
CAN−LOW
Example circuit
Wiring example
CG
CAN
LO HI
CG
CAN
LO HI
CG
CAN
LO HI
R
R
A
n
A
2
A
1
EL100−009
Terminating resistors of 120
W are not integrated and must be wired externally.
6.7.4
CAN on board
X35 − communication
Pin
Signal
Description
Data
Type: M12, 5−pole, A−coded, sockets
84DPSO05_5
1
n. c.
Not assigned
CAN specification
From HW version VD onwards, the 120
W
terminating resistor is integrated.
HW version: see C00210/10
2
n. c.
Not assigned
3
CG
CAN−Ground
4
CH
CAN−HIGH
5
CL
CAN−LOW
,
Software manual for the standard device / »Engineer« online help
Here, detailed information is provided about ...
ƒ
CAN communication;
ƒ
Parameter setting and configuration;
ƒ