Electrical installation − HighLine/StateLine version

Safety engineering

6

l

102

EDS84DPS424 EN 5.0

6.8

Safety engineering

Please observe the following safety instructions and application notes to preserve the
certified safety engineering features and to ensure trouble−free and safe operation.

}

Danger!

Danger to life through improper installation
Improper installation of safety engineering systems can cause an uncontrolled
starting action of the drives.
Possible consequences:

ƒ

Death or severe injuries

Protective measures:

ƒ

Safety engineering systems may only be installed and commissioned by
qualified and skilled personnel.

ƒ

All control components (switches, relays, PLC, ...) and the control cabinet
must comply with the requirements of ISO 138491 and ISO 13849−2. This
includes i.a.:
– Switches, relays with at least IP54 enclosure.
– Control cabinet with at least IP54 enclosure.
– Please refer to ISO 138491 and ISO 13849−2 for all further requirements.

ƒ

Wiring must be shielded.

ƒ

All safety relevant cables outside the control cabinet must be protected, e.g.
by means of a cable duct:
– Ensure that no short circuits can occur.
– For further measures see EN ISO 13849−2.

ƒ

If an external force acts upon the drive axes, additional brakes are required.
Please observe that hanging loads are subject to the force of gravity!

}

Danger!

Danger to life by improper installation
Improper installation of the safety equipment may cause an uncontrolled start
of the drives.
Possible consequences:

ƒ

Death or severe injury

Protective measures:
Shield the cables between the plugs for the safety equipment and the
connected components (e.g. sensors, devices, ...).

)

Note!

Please observe during transport, storage and operation:

ƒ

Cover unused connectors for control connections and interfaces with the
plastic covers provided to preserve the certified safety technology features.