Diagnostics, Danger – Lenze 8400 protec Manual User Manual
Page 162

Diagnostics
Display of operating data, diagnostics
Status display of the safety system via LEDs at the controller
l
162
EDS84DPS424 EN 5.0
Pos.
Colour
State
Description
DI7
yellow
on
DI7 = HIGH
off
DI7 = LOW
DI8
yellow
on
DI8 = HIGH
off
DI8 = LOW
DI9/DO3
yellow
on
DI9/DO3 = HIGH
off
DI9/DO3 = LOW
DI10/DO4
yellow
on
DI10/DO4 = HIGH
off
DI10/DO4 = LOW
DI11
yellow
on
DI11 = HIGH
off
DI11 = LOW
DI12
yellow
on
DI12 = HIGH
off
DI12 = LOW
DI13
yellow
on
DI13 = HIGH
off
DI13 = LOW
DI14
yellow
on
DI14 = HIGH
off
DI14 = LOW
10.1.3
Status display of the safety system via LEDs at the controller
Status display: drive−based safety
Pos.
Colour
State
Description
S−State
green
on
Communication between standard device and safety system
is running
blinking
Drive−based safety is in service status
off
Communication between standard device and safety system
is not possible
S−Error
red
on
Fault, trouble or warning
blinking
Drive−based safety is not accepted by the standard device
off
Error−free operation
S−Acknw
yellow
on
A parameter set acceptance must be acknowledged
S−Enable
yellow
on
Controller is enabled
blinking
Safety function is active (non−safe display)
The status of safety option 10 is solely shown via the "S−Enable" display. All other displays have no function.
}
Danger!
Danger to life due to wrong interpretation of the status display
A wrong interpretation of the status display of the drive−based safety may
result in dangerous operating statuses.
Possible consequences:
ƒ
Death or severe injuries
Protective measures:
ƒ
The status display of the drive−based safety must not be used for
safety−related purposes. The displays shown are unsafe.