beautypg.com

1 modem, 6 configuration – JUMO 705001 mTRON T - Central Processing Unit Operating Manual User Manual

Page 80

background image

6 Configuration

80

6.7.1

Modem

Setup dialog

Parameters

Parameter

Selection/settings

Description

Cycl. init. time

0 to 5 to 255 min

Time for cyclical initialization of the
modem (if the modem is switched on
after the system).

0 = one-time initialization (after system
has been switched on)

Init string

AT&FE0X3Q1&K0S0=1&D0&W0&Y0

(ASCII; max. 40 characters)

AT command for modem initialization

This default initialization string config-
ures the modem so that it can be called
from an external source, answers inde-
pendently, and receives Modbus com-
mands.

Call string

ATDT

(ASCII; max. 24 characters)

AT command for establishing a connec-
tion via the modem

ATDT = selection with dial tone (DTMF)

Hang-up string

ATH

(ASCII; max. 16 characters)

AT command for disconnection via the
modem

ATH (or ATH0) = hang up

Alarm message

Alarm type

Issue of alarm message

E-mail

In the event of an alarm, an e-mail is
sent (via the e-mail server after connect-
ing to the Internet).

PC visualization

In the event of an alarm, a modem con-
nection is established to a PC with pro-
cess visualization software.

?

?

?