3 variables, 1 analog variables, Variables – JUMO 705001 mTRON T - Central Processing Unit Operating Manual User Manual
Page 60: 6 configuration

6 Configuration
60
6.3
Variables
Variables are transferred using the serial interfaces (Com1, Com2; Modbus RTU) or LAN inter-
face (Ethernet; Modbus/TCP). During this process, the central processing unit can serve as a
Modbus master or Modbus slave.
Chapter 6.7 "Serial interface", page 78
Chapter 6.6 "Modbus/TCP", page 76
This means that up to 64 float variables, 64 integer variables, 64 digital variables, and 9 (ver-
sion 02: 27) text variables are available to be freely used in the system.
As of system version 02, a PROFIBUS-DP interface (slave) is also available which supports
the transfer of float and integer variables.
Chapter 6.8 "PROFIBUS (version 02)", page 83
6.3.1
Analog variables
64 analog variables are available (analog variables 1 to 64).
Setup dialog
Parameters
Parameter
Selection/settings
Description
Range start
-3.36E+38 to +9.0E+36
Start value for the range of the analog
variables
Range end
-3.36E+38 to +9.0E+36
End value for the range of the analog
variables
Retain
Retains the analog value in the event of power off
Not selected (empty)
Value is set to 0 after power on.
Selected (checkmark)
Value is retained.
Unit
Max. 5 characters (%)
Unit that is used to display the analog
value.