6 Configuration

68

6.4

Limit value monitoring

Up to 64 limit values can be monitored at the same time (limit value monitoring 1 to 64). One
of eight alarm functions can be selected for each limit monitoring, to monitor a freely selectable
input value (actual value) with respect to a fixed limit value or a limit value relating to the set-
point value (setpoint value

± limit value). Each limit monitoring provides an output signal.

Setup dialog

Parameters

Parameter

Selection/settings

Description

Alarm function

Inactive

Limit value monitoring is inactive

AF1

Limit value above and below the set-
point value (monitoring band around the
setpoint value)

AF2

As for AF1, output signal inverted

AF3

Limit value below the setpoint value

AF4

As for AF3, output signal inverted

AF5

Limit value above the setpoint value

AF6

As for AF5, output signal inverted

AF7

Fixed limit value

AF8

As for AF7, output signal inverted

Signal

suppression

Signal to activate alarm suppression

Inactive

No signal suppression

Module (source of signal)

Signal suppression by a signal (high
active) that must be selected in the fol-
lowing field (digital selector).

?