beautypg.com

6 modbus/tcp, Modbus/tcp, 6 configuration – JUMO 705001 mTRON T - Central Processing Unit Operating Manual User Manual

Page 76

background image

6 Configuration

76

6.6

Modbus/TCP

This menu is used to make settings for the Modbus TCP operating mode.
Chapter 8.2 "Modbus frames for reading", page 114
Chapter 8.3 "Modbus frames for writing", page 115
If the central processing unit is operating as the Modbus master, it can communicate with up to
four external devices (Modbus slaves; device 1 to 4). If it is operating as the Modbus slave, two
external devices (Modbus masters) can access the central processing unit at the same time.
Communication through the Modbus is described in more detail in the separate Modbus inter-
face description (B 705001.2.0).

Setup dialog

Parameters

Parameter

Selection/settings

Description

Modbus slave (central processing unit as Modbus slave)

Port

0 to 502 to 1024

TCP port for Modbus/TCP

Changes to the port are not applied until
after the system has been restarted.

Modbus master (central processing unit as Modbus master)

Timeout

60 to 2000 to 10000 ms

A request sent by the master is defined
as faulty if no answer is received within
this time.

Scanning cycle

60 to 500 to 99999 ms

The Modbus master requests the Mod-
bus master data from the Modbus slave
at these intervals.

IP-address

0.0.0.0

IP address of the external device (Mod-
bus slave)

The address must be set.

Port

0 to 502 to 1024

TCP port of the external device for Mod-
bus/TCP