12 Appendix

12.2

Cycle time, sampling rate, and shut-down time

Min.

Max.

Typical

PLC cycle time (FastTask)

1

7.5 ms

25 ms

(depending on tele-
gram repetitions)

10 ms

Adjustable PLC cycle time (Task)

2

50 ms

500 ms

-

System bus cycle time for

- Multichannel controller module

- 4-channel analog input module

- 8-channel analog input module

- Multifunction panel

30 ms

-

30 ms

System bus cycle time

1

for

- Relay module

- Digital input/output module

7.5 ms

-

10 ms

Multichannel controller module sampling
rate

2

-

-

50 ms

4-channel analog input module sampling
rate

2

-

-

50 ms

8-channel analog input module sampling
rate

2

-

-

375 ms

Relay module sampling rate

1

-

-

0 ms

Digital input/output module sampling rate

1

-

-

0 ms

Multifunction panel sampling rate

2

-

-

125 ms

Shut-down time (detection of module failure)
for

- Multichannel controller module

- 4-channel analog input module

- 8-channel analog input module

- Multifunction panel

-

-

100 to 750 ms

Shut-down time (detection of module failure)
for

- Relay module

- Digital input/output module

-

-

25 ms

1

Synchronous with system bus

2

Asynchronous with system bus