6 configuration – JUMO 705001 mTRON T - Central Processing Unit Operating Manual User Manual
Page 69

69
6 Configuration
Actual value
Analog signal as actual value (signal to be monitored)
Inactive
No signal selected.
Module (source of the analog signal)
The analog signal must be selected in
the following field (analog selector).
Setpoint value
Analog signal as setpoint value (reference signal for AF1 to AF6)
Inactive
No signal selected.
Module (source of the analog signal)
The analog signal must be selected in
the following field (analog selector).
Acknowledgem.
Condition for acknowledgement of the output signal (self-maintaining)
OFF
No acknowledgement required (output
signal is deactivated automatically if the
alarm condition is no longer present).
If inactive
Acknowledgement only possible if alarm
condition is no longer present.
Always
Acknowledgement always possible
Acknowledg.
signal
Signal to acknowledge the output signal
Inactive
No signal selected.
Module (source of signal)
Acknowledgement by means of a signal
(high active) that must be selected in the
following field (digital selector).
Hysteresis
function
Switching differential position around the limit value
Symmetric
Switching differential is positioned with
half above and half below the limit value.
Asymmetric left
Switching differential below the limit
value (typically)
Asymmetric right
Switching differential above the limit
value (typically)
Start-up alarm
suppression
Inactive
Limit value monitoring always operates
according to its alarm function.
Active
No alarm after power on or if limit value
or setpoint value is changed
Limit value
-3.37E+38 to 0 to +3.37E+38
Admissible deviation of the actual value
Switching
differential
0 to 1 to 99999
Switching thresholds of the output signal
(difference from limit value)
Switch-on delay
0 to 65535 s
Delay time for activation of the output
signal if alarm condition is present.
Switch-off delay
0 to 65535 s
Delay time for deactivation of the output
signal if alarm condition is no longer
present.
Pulse time
0 to 65535 s
Output signal is deactivated automati-
cally after this time.
Parameter
Selection/settings
Description
?
?