12 Appendix

148

12.1.3

Case and ambient conditions

12.1.4

Approval/approval marks

Conductor cross section (voltage supply)

Wire or strand without ferrule

Min. 1.5 mm

2

, max. 2.5 mm

2

Strand with ferrule

Min. 1.5 mm

2

, max. 2.5 mm

2

2 x strand with twin ferrule with plastic col-

lar

1.5 mm

2

Stripping length

10 mm

Electrical safety

Acc. to EN 61010-1

Overvoltage category III, pollution degree 2

Electromagnetic compatibility

Acc. to EN 61326-1

Interference emission

Class A – only for industrial use –

Interference immunity

To industrial requirements

Data backup

Buffered RAM

Buffer battery service life

Approx. 10 years (Lithium battery)

Case type

Metal case for DIN rail mounting in the control cabinet (indoor use);
DIN rail acc. to DIN EN 60715, 35 mm x 7.5 mm x 1 mm

Dimensions (W × H × D)

135 mm × 101 mm × 67.1 mm (without connection elements)

Weight (fully equipped)

Approx. 670 g

Protection type

IP20, acc. to DIN EN 60529

Ambient temperature range

-20 to +55 °C

Storage temperature range

-40 to +70 °C

Resistance to climatic conditions

Relative humidity

≤ 90 % annual average without condensation (cli-

matic class 3K3 acc. to DIN EN 60721-3-3 with extended tempera-
ture and humidity range)

Site altitude

Up to 2000 m above sea level

Mechanical ambient conditions

1

Classification acc. to DIN EN 60721-3-3, table 6, class 3M2

1

Test conditions are listed in the System Descripton B 705000.8.

Approval mark

Testing agency

Certificate/certifica-
tion number

Inspection basis

Valid for

c UL us

Underwriters Laborato-
ries

E201387

UL 61010-1 (3. Ed.),

CAN/CSA-22.2

No. 61010-1 (3. Ed.)

all types