beautypg.com

Maintenance, 1 controlling safe shutdowns, Controlling safe shutdowns – EUCHNER Safety Basic Monitor User Manual

Page 22

background image

22

Subject to reasonable modifications due to technical advances

Id.-No.: 114013

Issue date: 14.11.2011

EUCHNER GmbH + Co. KG

Kohlhammerstraße 16, D-70771 Leinfelden-Echterdingen

Tel. +49/711/7597-0, Fax +49/711/753316

Safety Basic Monitor

Maintenance

5.

Maintenance

5.1

Controlling safe shutdowns

The plant safety engineer is responsible for verifying that the Safety Basic Moni-
tor works correctly as part of the safety system.

At least once a year it is necessary to verify the safe shutdown by initiating asso-
ciated safety-related sensors or switchs:

Attention!

Press each safety-related AS-i slave and watch the reaction of the output circuits of the
AS-i Safety Monitor.

Attention!

Check the maximum activated time and the total operating time. These values depend
on the PFD value chosen for the total failure probability. Please refer to the information
in chap. Safety relevant data.

After reaching the projected maximum operating time (three, six, or twelve months) the
entire safety system must be checked for proper operation.

After reaching the projected total usage time (20 years) the device must be checked by
the manufacturer concerning its proper operation.