beautypg.com

Diagnostics, As-interface led indicators – Norgren VS18 Series Valve Advantage User Manual

Page 81

background image

VS18/VS26

MAINTENANCE & INSTRUCTION BOOKLET

8.6.8 Diagnostics

The VS18/VS26 AS-Interface slaves report missing +24V for the valves to the ASi master as a
peripheral fault. If the valve power is not present the red LED is blinking too.

8.6.9 AS-Interface LED indicators

ASI 1 (green) –

This LED will only be energised when the Network power is connected to the
Network connector, indicating that the ASi 1 logic circuit of the module is
powered.


DG 1 (red)

This LED indicates the status of the 1

st

ASi IC.


ASI 2 (green) –

This LED will only be energised when the Network power is connected to the
Network connector, indicating that the ASi 2 logic circuit of the module is
powered.


DG 2 (red)

This LED indicates the status of the 2

nd

ASi IC.


VA (green)

This LED will only be energised when 24 volts is applied to the valve power
terminal of the power supply connector.


Indicator status during powering up and commissioning

Condition

ASI 1

DG 1

ASI 2

DG 2

VA

Power

up

on on on on on

Device in a pre-operation state

on

on

on

on

on

Device in an operation state

on

off

on

off

on

Valve power is missing

on

blinking

on

blinking

off

VS2672926-KG00E_05/07 Page

81/97

This manual is related to the following products: