Profibus dp address and baud rate setting – Norgren VS18 Series Valve Advantage User Manual
Page 55
VS18/VS26
MAINTENANCE & INSTRUCTION BOOKLET
8.2.3 Profibus DP address and baud rate setting
The VS18/VS26 Profibus DP valve island address can be set within the range 1 to 99 (rotary
switch) resp. 125 (software). To set the address, use the selector switches accessible by
removing the securing screw and lifting the hinged cover of the address switches. The two
rotary switches allow an address range of 1 to 99. The valve island needs a power reset to
accept a new address. When position 0 is selected on both switches the address may be set
through software via a capable master.
Default address = 125
Following are VS18/VS26 Profibus DP baud rates, which are detected automatically:
9.60 kBit/s
19.20 kBit/s
45.45 kBit/s
93.75 kBit/s
187.50 kBit/s
500.00 kBit/s
1.50 MBit/s
12.00 MBit/s