Profibus dp wiring – Norgren VS18 Series Valve Advantage User Manual
Page 53
VS18/VS26
MAINTENANCE & INSTRUCTION BOOKLET
8.2.2 Profibus DP wiring
The bus line is specified in EN 50170 as line type A. It can be used as shown in the following
table. The table gives the bus parameters and line lengths of A and B type lines for comparison.
However it is recommended that only type A lines should be used, due to their expanded length
capabilities.
Line parameter
Parameter
Line A
Line B
Impedance in Ohm
135 to 165
100 to 130
Capacitance per unit length (pF/m)
< 30
< 60
Loop resistance (Ohm/km)
110
-
Core diameter (mm)
0.64
> 0.53
Core cross section (mm2)
> 0.34
> 0.22
Line lengths
Baud rate (kBit/s)
9.6
19.2
93.75
187.5
500
1‘500
12‘000
Line A (m)
1‘200
1‘200
1‘200
1‘000
400
200
100
Line B (m)
1‘200
1‘200
1‘200
600
200
-
-
Calculating possible line lengths
The maximum admissible distance between two bus stations in each Profibus network can be
calculated as follows:
(NO_REP + 1) * Segment length
NO_REP = The maximum number of repeaters connected in series (depends on repeater type).
Example:
The repeater manufacturer’s specifications allow nine repeaters to be connected in
series. The maximum distance between two bus stations at a data transfer rate of 1’500 kBit/s is
then as follows:
(9 + 1) * 200 m = 2’000 m
VS2672926-KG00E_05/07 Page
53/97