Profibus dp wiring – Norgren VS18 Series Valve Advantage User Manual

Page 53

background image

VS18/VS26

MAINTENANCE & INSTRUCTION BOOKLET

8.2.2 Profibus DP wiring

The bus line is specified in EN 50170 as line type A. It can be used as shown in the following
table. The table gives the bus parameters and line lengths of A and B type lines for comparison.
However it is recommended that only type A lines should be used, due to their expanded length
capabilities.

Line parameter

Parameter

Line A

Line B

Impedance in Ohm

135 to 165

100 to 130

Capacitance per unit length (pF/m)

< 30

< 60

Loop resistance (Ohm/km)

110

-

Core diameter (mm)

0.64

> 0.53

Core cross section (mm2)

> 0.34

> 0.22


Line lengths

Baud rate (kBit/s)

9.6

19.2

93.75

187.5

500

1‘500

12‘000

Line A (m)

1‘200

1‘200

1‘200

1‘000

400

200

100

Line B (m)

1‘200

1‘200

1‘200

600

200

-

-


Calculating possible line lengths

The maximum admissible distance between two bus stations in each Profibus network can be
calculated as follows:

(NO_REP + 1) * Segment length

NO_REP = The maximum number of repeaters connected in series (depends on repeater type).

Example:

The repeater manufacturer’s specifications allow nine repeaters to be connected in

series. The maximum distance between two bus stations at a data transfer rate of 1’500 kBit/s is
then as follows:
(9 + 1) * 200 m = 2’000 m