beautypg.com

Canopen led indicators – Norgren VS18 Series Valve Advantage User Manual

Page 69

background image

VS18/VS26

MAINTENANCE & INSTRUCTION BOOKLET

8.4.6 CANopen LED indicators

VB (green)

This LED will only be energised when 24 volts is applied to the electronics
power terminal of the power supply connector.


5V (green)

This LED will only be energised when the Network power is connected to the
Network connector, indicating that the logic circuit of the module is powered.


ER (red)

This LED indicates the status of the CAN physical and indicates errors due
to missing CAN messages (SYNC, GUARD or HEARTBEAT).


RN (red/green)–

This LED indicates the status of the CANopen network state machine.


VA (green)

This LED will only be energised when 24 volts is applied to the valve power
terminal of the power supply connector.


Indicator status during powering up and commissioning

Condition

VB

5V

ER

RN

VA

Power up

on

on

single flash

single flash
green/red

on

Autom. baud rate detection active

on

on

flickering

flickering green

on

Changing of address during
commissioning

on on flickering

flickering

green

on

Device in a pre-operation state

on

on

off

blinking green

on

Device in a stopped state

on

on

off

single flash
green

on

Device in an operation state

on

on

off

on green

on


Indicator status during CAN message Errors

Condition

VB

5V

ER

RN

VA

Too many error frames received

on

on

single flash

dependent on
device state

on

Heartbeat event has occurred

on

on

double flash

dependent on
device state

on

A sync message has not been
received

on

on

triple flash

dependent on
device state

on

Bus off

on

on

on

dependent on
device state

on

VS2672926-KG00E_05/07 Page

69/97