Wait until the end of the pre-heating
procedure. If the air temperature is
too low the unit will remain disabled
and the following message will be
shown:
Address : 1
DE-ICE PROCEDURE
------------------------
SYSTEM BLOCKED
TEMPERATURE TOO LOW
------------------------
PROBLEM
Error E1-AUTOPAN WITHOUT
LIMITS.
CAUSE
The two presets used as limits have
not been programmed.
SOLUTION
Program the two presets and then
update the Autopan configuration
menu (11.2 Saving the current
position (Preset), page 62 and 9.1.6.7
Autopan Menu, page 42).
PROBLEM
Error E2-WIPER BLOCKED.
CAUSE
The wiper is either jammed or
broken.
SOLUTION
Check that the wiper is free to
move; if the problem persists, seek
assistance.
PROBLEM
Error E3-PATROL WITHOUT
PRESET or error E4-PATROL, 1
PRESET ONLY.
CAUSE
The presets have not been
programmed.
SOLUTION
Program two or more presets and
then update the Patrol configuration
position (Preset), page 62 and 9.1.6.6
PROBLEM
Error E5-IR TEMP. TOO HIGH or
error E6-IR FAULT.
CAUSE
The infrared illuminator is not
working properly.
SOLUTION
Seek assistance.
PROBLEM
Error E7-PRST. NOT
CONFIGURED.
CAUSE
Recalling of a non programmed
preset.
SOLUTION
Save the preset using the relative
control (11.2 Saving the current
PROBLEM
Error E8-TOUR NOT
CONFIGURED.
CAUSE
Recalling of a non configured Tour.
SOLUTION
Save the Tour using the relative
control (11.6 Recalling a pattern
PROBLEM
Error E9-TEMP. TOO LOW.
CAUSE
The environment temperature is
too low.
SOLUTION
The movements of the P&T unit
is blocked to prevent mechanical
damage.