Red Lion C48C User Manual
Page 47
![background image](/manuals/408875/47/background.png)
8. OUTPUTS: (Output type and quantity, model dependent)
Solid-State:
NPN Open Collector: I
SNK
= 100 mA max. @ V
OL
= 1.1 VDC max.;
V
OH
= 30 VDC max.
PNP Open Collector: I
SRC
= 100 mA max.(See note);
V
OH
= 12 VDC ±15% (using internal supply); V
OH
= 13 to 30 VDC
(using external supply).
Note: The internal supply of the C48C can provide a total of 100 mA for
the combination of sensor current and PNP output sourcing current.
The supply voltage is +12 VDC (±15%), which will be the PNP output
voltage level when using only the internal supply.
If additional PNP output sourcing current or a higher output voltage
level is desired, an external DC supply may be connected between the
“DC Out/In” and “Comm.” terminals. This supply will determine the
PNP output voltage level, and must be in the range of +13 to +30 VDC.
An external supply can provide the additional output sourcing current
required in applications where two or more outputs are “ON”
simultaneously. However, the maximum rating of 100 mA per individual
output must not be exceeded, regardless of external supply capacity.
Relay: Form A contact, Rating = 5 A @ 250 VAC, 30 VDC (resistive load),
1/10 HP @ 120 VAC (inductive load)
Relay Life Expectancy: 100,000 cycles min. at max. load rating
Programmable Timed Output: User selectable output time resolution.
0.01 Second Resolution: 0.01 to 99.99 sec,
± 0.01% +20 msec max.
(Prescalers less than 2)
0.1 Second Resolution: 0.1 to 999.9 sec, ±100 msec
(Prescalers less than 2)
Note: For Prescaler values above 2, the timed delay output is affected by
the count speed (rate).
9. RS485 SERIAL COMMUNICATIONS (Optional): Up to 32 units can be
connected.
Baud Rate: Programmable from 1200 to 9600 baud
Address: Programmable from 0 to 99
Data Format: 10 Bit Frame, 1 start bit, 7 or 8 data bits, 1 or No Parity bit,
and 1 stop bit
Parity: Programmable for Odd (7 data bits), Even (7 data bits), or None (8
data bits)
10. CERTIFICATIONS AND COMPLIANCES:
SAFETY
UL Recognized Component, File #E137808, UL508, CSA C22.2 No. 14
Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.
Type 4X Indoor Enclosure rating (Face only), UL50
IEC 1010-1, EN 61010-1: Safety requirements for electrical equipment for
measurement, control, and laboratory use, Part 1.
IP65 Enclosure rating (Face only), IEC 529
ELECTROMAGNETIC COMPATIBILITY
Notes:
AC VERSIONS
1. A power line filter, RLC#LFIL0000 or equivalent, was installed when the
unit was DC powered.
DC VERSIONS
To insure compliance with the EMC standards listed above, do not connect
any wires from the terminal(s) labeled “COMM.” to the “DC-” supply
terminal (12), when powering the unit from a DC supply.
Refer to EMC Installation Guidelines section of the manual for additional
information.
-41-
Enclosure class A
EN 55011
RF interference
Emissions to EN 50081-2
Level 3; 10 V/m
ENV 50204
Simulation of cordless telephone
150 KHz - 80 MHz
Level 3; 10 V/rms
EN 61000-4-6
RF conducted interference
Level 3; 2 Kv power
Level 4; 2 Kv I/O
EN 61000-4-4
Fast transients (burst)
80 MHz - 1 GHz
Level 3; 10 V/m
EN 61000-4-3
Electromagnetic RF fields
Level 3; 8 Kv air
Level 2; 4 Kv contact
EN 61000-4-2
Electrostatic discharge
200 Hz, 50% duty cycle
Immunity to EN 50082-2
900 MHz ± 5 MHz