Troubleshooting

118

3078

Diag get drive 0 status failed
(Failed to get drive status, communication

error.)

Press the Enter button to reboot.

Ensure the drive shows good status

through the drive status window.

Deactivate the drive using the GUI control

panel maintenance menu.

Reseat drive.

Check cabling.

Load/unload a cartridge to the drive to

verify.

Check the tape cartridge used in the last

operation for damage.

Run the cartridge cycle diagnostic to

verify.

3079

Diag get drive 1 status failed
(Failed to get drive status, communication

error.)

Press the Enter button to reboot.

Ensure the drive shows good status

through the drive status window.

Deactivate the drive using the GUI control

panel maintenance menu.

Reseat drive.

Check cabling.

Load/unload a cartridge to the drive to

verify.

Check the tape cartridge used in the last

operation for damage.

Run the cartridge cycle diagnostic to

verify.

Table 10

Fault Symptom Codes (continued)

FSC

Message

ERP