Connection values “Additional In-/Outputs”
Position feedback 4 to 20 mA
Terminals for AI1:
31+ / 32-
supply voltage:
DC 8 ... 36 V
signal range
3.8 ... 21.5 mA
0 % and 100 % configurable
device fault
< 1mA
Terminals for AB1:
81+ / 82-
1 Binary output alarm, galvanically separated, two-wire
system, according to DIN 19234, for external supply
supply voltage
DC 8 ... 36 V
Logic: no alarm
< 1 mA
alarm
> 2.2 mA
device fault
< 50 µA
Binary Input
Terminals for EB1:
13+ / 14-
Terminals for EB2:
15+ / 16-
A connected switch is loaded with 3 V, 150
µA.
Switch 1 Switch 2
Actuator control function
close
close
normal operation
open
close
go to stop at
0 %
close
open
go to stop at 100 %
open
open
hold last position
Requirements for connected switches:
Capacitance in parallel
< 100 nF
Resistivity for ON
< 2 kOhm
Resistivity for OFF
>10 kOhm
Hysteresis
2 ... 5 kOhm
Binary outputs
Terminals for AB1:
81+ / 82-
Terminals for AB2:
83+ / 84-
two-wire system, according to DIN 19234, for external
supply
supply voltage
DC 8 ... 36 V
Logic:
limit value not exceeded
< 1 mA
limit value exceeded
> 2.2 mA (typ. 6 mA)
device fault
< 50 µA
configurable as switch output:
limit value not exceeded
< 50 µA
limit value exceeded
> 20mA / 20 V
> 40mA / 10 V
Potentiometer (in preparation)
Sensor (in preparation)
Built-in Limit Switch
Terminals for GW1:
41+ / 42-
Terminals for GW2:
51+ / 52-
in two-wire-technique acc. to DIN 19234 with external
power supply for connection to switching amplifier, or in
three-wire-technique
Current consumption
vane clear
> 2.2 mA
vane interposed
< 1 mA
for control circuit with the following electrical values
supply voltage
DC8 V, Ri ca. 1 kOhm
supply voltage range
DC 5...25 V
residual ripple
< 10 % p.p.
permissible line resistance
< 100 Ohm
Response characteristic
1) 2)
switching differential
1%
switching point repeatability 0.2 %
Non intrinsic safe and EEx d - Input circuit
Max. electrical Power Pmax = 2,5 W
Terminals and cable glands Umax = 60 V
Self-heating-up of housing surface 1.3 K/W
Additional In-/Outputs EEx d
(will follow)
EEx i - Input circuit
Input circuit max. values
HART / FoxCom / 4-20 mA:
Ui= 30 V, Ii= 130 mA, Pi= 0.9 W, Ci= 1.3 nF, Li= 5 µH
FOUNDATION Fieldbus / PROFIBUS:
Ui= 24 V, Ii= 380 mA, Pi= 5.2 W, Ci= 1.3 nF, Li= 5 µH
Additional In-/Outputs EEx i
Option:
Position feedback
Ui= 16 V, Ii= 80 mA, Pi= 250 mW, Ci= 26 nF, Li= 5 µH
Binary Input
Uo= 7.88 V, Io= 11.4 mA, Po= 23 mW
B
II
C
II
Lo [mH]
Co [µF]
Lo [mH]
Co [µF]
100
0.72
100
3.9
10
1.1
10
5.5
1
1.6
1
8.7
0.1
2.7
0.1
15
0.01
4.7
0.01
27
(Li and Ci integrated)
Binary Output
Ui= 16 V, Ii= 80 mA, Pi= 250 mW, Ci= 26 nF, Li= 5 µH
Potentiometer
(will follow)
Sensor
(will follow)
Limit switches
Ui= 16 V, Ii= 25 mA, Pi= 64 mW, Ci= 30 nF, Li= 100 µH
1)
Data measured according to VDI/VDE 2177
2)
With stroke 30 mm and lever length 90 mm