Electrical connections, Electrical connections 28 – Badger Meter SRD/SRI Valve Positioners User Manual
Page 28

ELECTRICAL CONNECTIONS
Observe
"Safety Requirements" on page 66
can be supplied with cable gland—please verify marking at
housing!
Unused cable entries must be closed with blanking plugs
with the appropriate explosion-proof certification (the plastic
plugs are only to avoid damage on shipping)
Feed in the bus cable through the gland 1 The gland is
suitable for cable diameters of 6…12 mm (0 24…0 47 in)
Observe the tightness of the cable entry
Make the electrical connection of the input line at the screw
terminals 3, whereby with Fieldbus devices no polarity has
to be observed The terminals are suitable for wire cross-
sections of 0 3…2 5 mm
2
(22…14 AWG)
For devices with communication, the shield of the bus
connection is:
• with conductive cable glands (recommended) directly
connected with the housing
• with non-conductive cable glands to be placed onto the
inner screw terminal 4
NOTE:
N
When connecting shielded cable, connect the
cable shield on both sides (on the positioner as well
as on the system side) For selection of cable, see
recommendation for cable types according to IEC
1158-2
For connection to a local ground, the internal and external
ground terminal 4 can be used
Page 28
Electrical Connections
August 2014
POS-UM-00009-EN-02