Badger Meter SRD/SRI Valve Positioners User Manual
Page 38
![background image](/manuals/371282/38/background.png)
Menu 2: Autostart
M
1
2
3
4
½
-
½
-
-
M and LED 2 flash
Selection between different Autostart modes
(change with key (
+) or (–) : )
Autostart:
To automatically adapt the positioner to the valve. Geometric data of the
actuator is determined and optimally assigned to control parameters. If the
"Standard" Autostart does not result in stable regulation, another Autostart
mode - depending upon actuator - should be selected. At
initial start-up,
an Autostart should always be performed.
Attention: Autostart overwrites previous control parameters!
2.2 Ready for "Standard" Autostart:
-
1
-
-
1
LED 1 and LED 4 lights up
With key (
+) or (–) to other Autostart modes:
2.1 Ready for "End points" Autostart:
Serves for automatic adjustment of the SRD to the mechanical end points.
-
-
1
1
-
LED 2 and LED 3 lights up
2.3 Ready for "Enhanced" Autostart:
To the optimization of the controller parameters in relation to standard mode:
-
-
1
-
1
LED 2 and LED 4 lights up
2.4 Ready for "Smooth response" Autostart:
Extended, damped controller parameters for e.g. smaller drives
-
1
-
1
-
LED 1 and LED 3 lights up
2.5 Ready for "Fast response" Autostart:
Extended, undamped controller parameters for e.g. larger drives
-
1
1
-
-
LED 1 and LED 2 lights up
After selection and start (by pressing the ( ) key) the function taking
several minutes can be followed at LCD or the green LEDs.
Duration on a valve position can take some time depending on actuator
volume, air supply, pressure, etc.
-
1
-
-
-
LED 1 lights up
Moving direction, mechanical starting and ending positions are determined
by one or several passages of valve position range.
-
-
1
-
-
LED 2 lights up
Ramps are entered and control system parameter is determined (ratio
position/valve size).
-
-
-
1
-
LED 3 lights up
Jumps are entered for determination of control parameters.
-
-
-
-
1
LED 4 lights up
Determination of positioning speeds.
-
-
-
-
-
All LEDs are off
Determined values are saved; previous values are superscribed. The
SRD is IN SERVICE again with the detected new parameters.
SRD Main Menu
1 Mounting
2 Autostart
3 Valve Action
2 Autostart
2.1 Endpoints
2.2 Standard
2.3 Enhanced
2 Autostart
2.3 Enhanced
2.4 Smooth resp.
2.5 Fast resp.
2 Autostart
SRD960 Vers.xx
Get end points
2 Autostart
SRD960 Vers.xx
Get motor gain
2 Autostart
SRD960 Vers.xx
Control params
2 Autostart
SRD960 Vers.xx
Get valve speed
Page 38
Startup
August 2014