Badger Meter SRD/SRI Valve Positioners User Manual
Page 62

LEDs
Description of message / LCD text
Remedy
M
1
2
3
4
¾
-
-
-
¼
Autostart err 1
Message 8:
AUTOSTART
defective
y
l
p
p
u
s
ri
a
k
c
e
h
C
w
o
l
o
o
t
y
l
p
p
u
s
ri
A
Feedback lever (linear actuator) or Coupling (rotary
actuator) incorrectly linked. Potentiometer moves out
of operating range of ± 47 % of 0° position
Check mounting.
Flat area points to arrow on housing
Coupling (rotary actuator) incorrectly linked
(R and L interchanged)
Check mounting
Pneumatic output to actuator closed or untight/
When direct mounting onto FlowTop or FlowPak,
the screw plug y1-d is not removed.
Check pneumatic connections
Mechanical stops not determinable
Check spring movement of actuator /
check air supply / Check mounting
When using a booster or spool valve, no control
parameters can be determined, since air capacity
is too high.
Device version is not suitable for this actuator; se-
lect version with smaller air capacity or remove
booster.
Control parameter too high since air capacity is too
high (in general, oscillation in valve movement)
Use a booster or the version with spool valve. Re-
duce control parameter prop.-gain (Menu 6.1 and
6.2) to Code 10 = value 26.6.
Possibly incomprehensible configuration data
Reset configuration, see Menu 9.1
M
1
2
3
4
¾ ¼
-
-
¼
Autostart err 2
Message 9:
AUTOSTART
defective
Configuration to single-acting instead of
double-acting actuator
Initialize factory calibration for double-acting in
Menu 9.7
M
1
2
3
4
¾
-
¼
-
¼
Optionboard err
Message 10:
Disturbances at
Option board
Configured status of the SRD deviates from
existing version (e.g. Option board has been
inserted subsequently.
Check if correct option board has been connected
Confirm message and thereby new instrument
version.
d
e
g
n
a
h
c
r
e
t
n
i
s
l
a
n
i
m
r
e
t
o
t
s
n
o
it
c
e
n
n
o
C
t
c
a
t
n
o
c
d
a
B
Check connections
Tighten electronics
d
r
a
o
b
n
o
it
p
o
e
g
n
a
h
c
x
E
e
v
it
c
e
f
e
D
M
1
2
3
4
¾ ¼ ¼
-
¼
Ctrl diff error
Message 11:
Remaining control
deviation
Actuator problems (high friction or blocked)
Check actuator
r
e
tl
if
ri
a
/
y
l
p
p
u
s
ri
a
k
c
e
h
C
y
l
p
p
u
s
ri
a
t
n
e
i
c
if
f
u
s
n
I
Insufficient parametes for position controls,
for example, amplification too small
Check control paramter,
check pneumatic components
IP module or pneumatic amplifier defect
Check in Menu 7; replace if necessary
M
1
2
3
4
¾
-
-
¼ ¼
Lower stroke lim
Message 12:
configurated
closing limit has
been reached
If this is desired, the message may be ignored, of
course.
If not, the setting has to be checked via
communication
M
1
2
3
4
¾ ¼
-
¼ ¼
Upper stroke lim
Message 13:
configurated
opening limit has
been reached
If this is desired, the message may be ignored, of
course.
If not, the setting has to be checked via
communication
Page 62
Troubleshooting Guide
August 2014
POS-UM-00009-EN-02