Recordall® Compound Series Meters

Door Seal Replacement

User Manual

RCS-UM-00075-EN-02 (September 2013)

DESCRIPTION

The door seal in the valve assembly for the 2" and 3" Compound Series meters is replaceable, should it become necessary,

with the use of the Door Seal Replacement Tool Kit (64201-001.) This instruction sheet provides step-by-step instructions for

using this kit. The 4" and 6" valve assemblies do not permit door seal replacement. If service or replacement is required, a new

complete valve assembly must be installed.

DOOR SEAL REPLACEMENT PROCEDURE

Disassembling the Unit

1. Remove the bolts from the cover assembly and lift the cover

off the housing. Removing the cover assembly exposes the

valve assembly for service.

2. Remove the lock pawl.
3. Turn the valve assembly counter-clockwise to unscrew it from

the housing, then lift it out of the housing.

4. Remove the door seal bolt, nut and washers from the

valve assembly.

5. Place one of the spacer bolts through the spacer and into the

threaded hole on the back of the valve assembly.

6. Use a wrench to turn the bolt head clockwise to open the

door about 1/2", exposing the door seal.

The kit is made up of a spacer and 2 bolts—

one with a washer for a 2" meter, and a larger

bolt with no washer for a 3" meter.

Valve

Assembly

Lock Pawl

Cover

Assembly

Bolt

Nut

Replacing the Door Seal

7. Replace the old seal with the new seal.
8. Turn the spacer bolt counter-clockwise until the door closes while maintaining alignment between the seal and the door.
9. Completely remove the bolt/washer and spacer.

Threaded

Hole

Small Hole Up

Spacer Bolt

Through Spacer

Door Open

Seal Exposed

Seal

Replaced