Operation
After Power ON
INIT: After power on of input signal or after reset, the SRD
initializes, thus the various components of the electronic are
checked and started (The stored data of the positioner is of
course not affected and remains unchanged)
The current status is stated on the LCD in clear text or
indicated as LED code
Initialization after positioner startup takes approximately 3
seconds, then the SRD goes:
• Into operation (Autostart has already been done) or
• To configuration, Menu 1 (with LCD the text language
is selected before [for example, changing to German
language])
9.9 Menu Lang
9.9.1 English
9.9.2 Deutsch
9.9.3 (Francais)
... and the display orientation is selected ...
9.10 LCD Orient
9.10.1 Normal
9.10.2 Flipped
... then automatically continued to configuration:
SRD Main Menu
1 Mounting
2 Autostart
3 Valve Action
Select with keys
(+) or (–)
and confirm with
( ) .
Configuration Menus
The various specifications for configuration are arranged
in menus:
LEDs flash
Menu Description
red
green
M
1
2
3
4
½ ½
1
Actuator system,
mounting side
½
½
2
Autostart
½
½
3
Valve function
½
½
4
Characteristic of setpoint
½ ½ ½
5
Limits and Alarms
½ ½
½
6
Parameter for
position controller
½ ½
½
7
Manual setting of
pneumatic output
½
½ ½
8
Manual setting of
valve position
½
½
½
9
Calibration functions
for workshop
½
½ ½
10
PROFIBUS-PA:Bus Address
FOUNDATION F.:Simulate
½ = ON and OFF flashing same duration
Details of Menus and Parameters are on the following pages
While in Operation
After autostart, the SRD goes automatically IN OPERATION
(Additional parameters can of course be configured by
pressing the menu key ()
87.5 %
Valve position
On the LCD display the process variable
is indicated
With LED version, all LEDs are off during
operation
Travel position
Input current
Digital setpoint
Stem setpoint
Output pressure1
Output pressure2
Input pressure
Temperature
Travel sum
Valve cycles
SRD Version
By pressing keys (+) or (–), additional
information can be retrieved from
the SRD:
Certain data is available only with the
corresponding options
Manual Operation
By pressing the key () twice, the SRD goes into manual
operation mode, where the valve position can be set
manually Exit the menu by pressing () twice
Diagnostics During Operation
87.5 %
Valve position
Ctrl diff error
If the diagnostics determines an
occurrence, this is indicated in the
bottom line: (blinking code with LEDs)
Message
The SRD recognizes an occurrence which the user must
eliminate by taking suitable steps in order to continue with
operation This can be, for example, a wrong configuration
or missing supply air Press the key (+) to retrieve
additional information
Error
During self-testing the SRD recognized an error and is no
longer operable
Page 33
Startup
August 2014