Precision air conditioning smartcool™ 6 - 200kw, Technical data sr c000 units, Electrical data – Airedale SmartCool 11-233kW User Manual
Page 91

SR12D045-C000
SR12D045-C000-0
SR12D045-C000-1
SR12D045-C000-2
Unit Data - Full Function
(1)
Nominal Run Amps
A
35.8
35.2
64.7
Recommended Mains Fuse Size
A
50
50
80
Unit Data - Cooling Only
Nominal Run Amps
A
5.43
5.43
9.5
Recommended Mains Fuse Size
A
10
10
16
Max Mains Incoming Cable Size
mm²
35
35
70
Mains Supply
V
400V / 3PH + N / 50Hz
380V / 3PH + N / 60Hz
220V / 3PH / 60Hz
Control Circuit
VAC
24
24
24
Evaporator Fan - Motor - Per Fan
Motor Type
EC
EC
EC
Quantity x Motor Size
(2)
kW
1 x 2.9
1 x 2.9
1 x 2.9
Full Load Amps
A
4.5
4.5
7.5
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat
2
2
2
Number of Elements
6
6
6
Rating
kW
15
13.54
15
Current Per Phase
A
21.7
20.6
39.4
Humidifier
Capacity
kg/hr
8
8
8
Rating
kW
6
6
6
Full Load Amps
A
8.7
9.2
15.8
First upgrade EC Motor - Per Fan
Quantity x Motor Size
kW
N/A
N/A
N/A
Full Load Amps
A
N/A
N/A
N/A
Technical Data SR C000 Units
Electrical Data
(1) Values given for full function units with standard selections for heating, humidification, supply air fans.
(2) Stated motor power is based on maximum electrical power absorbed
Precision Air Conditioning
SmartCool™ 6 - 200kW
91
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.1.0_04_2014
Te
ch
nic
al
C0
C0
C
000
SR