Precision air conditioning smartcool™ 6 - 200kw, Ins ta lla tio n, Packed dimensions – Airedale SmartCool 11-233kW User Manual
Page 53

Packed Dimensions
For specific markets units shall be shipped, mounted on
wooden pallet and covered with polythene. The pallet shall
be mechanically fixed to the unit for transportation only
(Please contact Airedale for this option). Add 50mm to
length and width, 160mm to height.
D
Positioning
Minimum Unit Clearance SN, SR
Open and Enclosed Floorstand Option
A
B
C - Floorstand
(3)
SN06D
mm
684
600
Min 350 – Max 750
(+ 50mm Feet Adjustable +/-20mm)
(4)
SN09D / SR09D
mm
963
880
SN12D / SR12D
mm
1242
880
SR15D
mm
1521
880
SR18D
mm
1800
880
Minimum Ceiling Clearance- (D)
Forward Only
Forward and 1 Side
Forward and 2 Sides
All Faces
SN06D
mm
720
500
380
250
SN09D / SR09D
mm
720
500
380
250
SN12D / SR12D
mm
720
500
380
250
SR15D
mm
740
550
440
280
SR18D
mm
750
590
480
300
(1) Shown with optional open floor stand.
(2) Shaded area indicates minimum service and maintenance requirements. The unit must be installed with allowance for carpet tile clearance.
(3) Dimension C denotes recommended minimum/maximum floor stand height, refer to Airedale for special applications, please specify at order.
(4) Min = Threaded foot at minimum extension (additional to “C” dimension).
Max = Threaded foot at maximum extension (additional to “C” dimension).
Precision Air Conditioning
SmartCool™ 6 - 200kW
53
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.1.0_04_2014
Ins
ta
lla
tio
n