Controls
Password Protection
The control system integrity shall be maintained by restricting access with a password PIN number.
IMPORTANT
To change the PIN , please contact Airedale at time of order with the preferred 4 digit number.
Remote On/Off
Terminals for interlocking shall be provided to enable or disable the unit remotely.
Fire Shut Down
Terminals for interlocking shall be provided to shut down the unit in the event of fire.
Evaporator Fan Hours Run Log & Reset
Shall allow the user to monitor the running times of the evaporator fans and reset after maintenance.
Hours run log or visual service indicator shall be provided.
Evaporator Fan Speed Control
Evaporator fan speed control shall be easily set via the display keypad and can be incrementally increased or decreased
to meet on site airflow and external static pressure requirements.
Filter Change Alarm
Filter change shall be managed by the software, and shall be based on fan(s) hours run with an alarm being generated
when the pre-set run time limit has been exceeded. The set-point value shall be adjusted to suit each application and is
factory set to 4000 hours.
Precision Air Conditioning
SmartCool™ 6 - 200kW
29
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.1.0_04_2014