Technical Data SR C0C0 Units
Electrical Data
SR12D035-C0C0
(1) Values given for full function units with standard selections for heating, humidification, supply air fans.
(2) Stated motor power is based on maximum electrical power absorbed
SR12D035-C0C0-0
SR12D035-C0C0-1
SR12D035-C0C0-2
Unit Data - Full Function
(1)
Nominal Run Amps
A
19.6
19.2
35.2
Recommended Mains Fuse Size
A
25
25
50
Unit Data - Cooling Only
Nominal Run Amps
A
5.43
5.43
9.5
Recommended Mains Fuse Size
A
10
10
16
Max Mains Incoming Cable Size
mm²
16
16
35
Mains Supply
V
400V / 3PH + N / 50Hz
380V / 3PH + N / 60Hz
220V / 3PH / 60Hz
Control Circuit
VAC
24
24
24
Evaporator Fan - Motor - Per Fan
Motor Type
EC
EC
EC
Quantity x Motor Size
(2)
kW
1 x 2.9
1 x 2.9
1 x 2.9
Full Load Amps
A
4.5
4.5
7.5
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat
1
1
1
Number of Elements
3
3
3
Rating
kW
7.5
6.8
7.5
Current Per Phase
A
10.9
10.3
19.7
Humidifier
Capacity
kg/hr
3
3
3
Rating
kW
2.25
2.25
2.25
Full Load Amps
A
3.3
3.5
6
First upgrade EC Motor - Per Fan
Quantity x Motor Size
kW
N/A
N/A
N/A
Full Load Amps
A
N/A
N/A
N/A
Precision Air Conditioning
SmartCool™ 6 - 200kW
115
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.1.0_04_2014
Te
ch
nic
al
C0
C0
C0
C0
SR