Smartcool™ 6 - 200kw precision air conditioning, Technical data sd cl00 units, Te ch ni ca l sd c l0 0 – Airedale SmartCool 11-233kW User Manual
Page 144: Performance data sd cl00

Technical Data SD CL00 Units
Performance Data SD CL00
Chilled water inlet and outlet temperatures
Air On
5 / 10 °C
7 / 12 °C
8 / 14 °C
10 / 16 °C
Temp. (°C)
TC
SC
TC
SC
TC
SC
TC
SC
/ %RH
(kW)
(kW)
(kW)
(kW)
(kW)
(kW)
(kW)
(kW)
22 / 50
124.1
96.5
97.5
84.2
74.8
72.3
59.3
59.3
SD18D115-CL00-0
24 / 45
139.2
109.3
112.7
97.2
89.7
83.7
73.4
73.4
26 / 40
152.1
122.1
125.8
110.1
103.0
96.4
86.9
86.9
22 / 50
152.0
115.9
120.9
101.3
97.2
90.4
73.0
73.0
SD22D145-CL00-0
24 / 45
169.8
130.9
138.7
116.5
115.7
106.1
89.4
89.4
26 / 40
184.9
145.9
154.1
131.6
131.5
121.5
105.2
105.2
22 / 50
199.1
151.8
158.7
132.8
128.6
118.8
96.2
96.2
SD25D180-CL00-0
24 / 45
222.1
171.4
181.8
152.7
152.4
139.2
117.5
117.5
26 / 40
241.9
191.1
201.7
172.5
172.9
159.4
137.9
137.9
22 / 50
256.3
196.6
203.8
171.9
164.0
153.5
123.8
123.8
SD31D235-CL00-0
24 / 45
286.3
222.1
233.9
197.7
195.1
180.0
151.4
151.4
26 / 40
312.1
247.7
259.8
223.5
221.7
206.3
177.9
177.9
22 / 50
297.7
227.0
237.7
198.7
193.2
177.9
144.1
144.1
SD35D270-CL00-0
24 / 45
332.2
256.4
272.1
228.3
228.7
208.3
175.7
175.7
26 / 40
361.6
285.6
301.7
257.8
259.0
238.4
206.1
206.1
SmartCool™ 6 - 200kW
Precision Air Conditioning
144
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.1.0_04_2014
Te
ch
ni
ca
l
SD
C
L0
0