Smartcool™ 6 - 200kw precision air conditioning, Ins ta lla tio n, Positioning – Airedale SmartCool 11-233kW User Manual
Page 54

Positioning
A
B
C - Floorstand
(3)
SD18D
mm
1800
880
Min 600– Max 750
SD22D
mm
2200
880
SD25D
mm
2500
880
SD31D
mm
3100
880
SD35D
mm
3500
880
Minimum Ceiling Clearance- (D)
Forward Only
Forward and 1 Side
Forward and 2 Sides
All Faces
SD18D
mm
720
500
380
250
SD22D
mm
720
500
380
250
SD25D
mm
720
500
380
250
SD31D
mm
740
550
440
280
SD35D
mm
750
590
480
300
(1) Shown with standard open floor stand.
(2) Shaded area indicates minimum service and maintenance requirements. The unit must be installed with allowance for carpet tile clearance.
(3) Dimension C denotes recommended minimum/maximum floor stand height, refer to Airedale for special applications, please specify at order.
Minimum Unit Clearance SD
Open and Enclosed Floorstand Option
SmartCool™ 6 - 200kW
Precision Air Conditioning
54
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.1.0_04_2014