Inputs InP.1 and InP.2

Name

Value range Description

I.Fnc

function

0

no function

1

heating current input

2

External setpoint

4

2nd process value X2

6

no controller input

7

process value X1

S.tYP

sensor type

0

Thermocouple type L (-100...900°C), Fe-CuNi DIN

1

Thermocouple type J (-100...1200°C), Fe-CuNi

2

Thermocouple type K (-100...1350°C), NiCr-Ni

3

Thermocouple typeN (-100...1300°C), Nicrosil-Nisil

4

Thermocouple type S (0...1760°C), PtRh-Pt10%

5

Thermocouple type R (0...1760°C), PtRh-Pt13%

6

Thermocouple type T (-200...400°C), Cu-CuNi

7

Thermocouple type C (0...2315°C), W5%Re-W26%Re

8

Thermocouple type D (0...2315°C), W3%Re-W25%Re

9

Thermocouple type Typ E (-100...1000°C), NiCr-CuNi

10

Thermocouple type Typ B (0/100...1820°C), PtRh-Pt6%

18

special thermocouple (Linearization necessary)

20

Pt100 (-200.0 ... 100,0 (150)°C)

21

Pt100 (-200.0 ... 850,0 °C)

22

Pt1000 (-200.0...850.0 °C)

23

Special 0...4500 Ohm (default as KTY11-6)

24

Special 0...450 Ohm

25

Special 0...1600 Ohm

26

Special 0...160 Ohm

30

Current 0/4...20mA

31

Current: 0...50 mA AC (HC input Inp2 only)

40

Voltage 0...10V / 2...10 V (Inp1 only)

41

Special (-2,5...115 mV)

42

Special (-25...1150 mV)

43

Special (-25...90 mV)

44

Special (-500...500 mV)

45

Special (-5...5 V) (Inp1 only)

46

Special (-10...10 V) (Inp1 only)

47

Special (-200..200 mV)

50

Potentiometer 0...160 Ohm

51

Potentiometer 0...450 Ohm

52

Potentiometer 0...1600 Ohm

53

Potentiometer 0...4500 Ohm

4wir

Resistance connection type(only for Inp.1)

0

3 wire connection

1

4 wire connection

S.Lin

linearization

0

no linearization

1

special linearization

Corr

measured value correction

0

no correction

1

offset correction

2

2-point correction

3

scaling

In.F

OFF,

-1999...9999

alternative value INP

fAI1

(fAI2)

Forcing of analog input INP1, INP2

µ (only visible with BlueControl

Ò

!)

0

not active

1

the value for this analog input is defined via interface.

Configuration level

KS 45

55