2 error status self-tuning 33 – West Control Solutions KS 45 User Manual

Page 33

background image

Name

Description

Cause

Possible remedial action

AdA.H Self-tuning heating

alarm
(ADAH)

See Self-tuning heating error
status

see Self-tuning heating error status

AdA.C Self-tuning heating

alarm cooling
(ADAC)

See Self-tuning cooling error
status

see Self-tuning cooling error status

Lim.1 Latched limit value

alarm 1

Adjusted limit value 1 exceeded Check process

Lim.2 Latched limit value

alarm 2

Adjusted limit value 2 exceeded Check process

Lim.3 Latched limit value

alarm 3

Adjusted limit value 3 exceeded Check process

Inf.1 Time limit value

message

Preset number of operating
hours reached

Application-specific

Inf.2 Switching cycle

message
(digital outputs)

Preset number of switching cy-
cles reached

Application-specific

g

Latched alarms Lim1/2/3 (E-element displayed) can be acknowledged, i.e. reset via digital alarm di1.

For Configuration, see page :

ConF / LOGI / Err.r

g

When an alarm is still pending, i.e. unless the error cause was removed ( E display blinks), latched alarms
cannot be acknowledged and reset.

g

If sensor errors should not be on the error list any more after error correction without manual reset in the
error list, suppression via BlueControl

Ò

is possible by means of setting ILat.

CONF / othr / ILat

1

blocked

This setting is without effect on limit values Lim.1 … 3 configured for storage.

6.9.2

Error status self-tuning

Self-tuning heating (

ADA.H) and cooling ( ADA.C) error status:

Functions

KS 45

33

Maintenance manager / error list

Error-state

Signification

2

Pending error

Change to error status 1after error removal

1

Stored error

Change to error status 0 after acknowledgement in error list 0

0

no error/message

Not visible, except during acknowledgement